THE FOLLOWING LISTS THE FAULT CODES FOR THE VAILLANT ECOTEC RANGE OF BOILERS , JUST CHECK WHAT THE BOILER DISPLAY IS SHOWING, IT SHOULD BE A F WITH A NUMBER FOLLOWING IT. THEN COMPARE IT WITH THE LIST AND IT WILL SHOW YOU WHAT THE MEANING AND THE CAUSE OF THE FAULT IS.

PLEASE NOTE THAT YOU MUST BE GAS SAFE REGISTERED TO WORK ON GAS APPLIANCES, PLEASE CALL US IF YOU ARE UNSURE AND WE CAN ADVISE OR SEND A ENGINEER TO REPAIR THE BOILER.

        Code.                   Meaning.   &  Cause


F. 0                         Flow–NTC open circuit
                                NTC broken, NTC cable broken, Defective connection at NTC,
                                Defective connection at electronics
F. 1                         Return–NTC open circuit NTC broken, NTC cable broken, Defective connection at NTC,
                                Defective connection at electronics
F.10                        Flow NTC short circuit NTC defective, short circuit in cable harness, cable/casing shortcut
F.11                         Return NTC short circuit NTC defective, short circuit in cable harness, cable/casing shortcut
F.13                         Tank NTC short circuit NTC defective, short circuit in cable harness, cable/casing shortcut
F.20                         Safety temperature limiter by NTC activated
                                Flow-NTC not correctly thermal-connected or defective; appliance
                                does not shut down
F.22                         Dry fire
                                 Too little water in the appliance, water pressure sensor defective,
                                cable to pump or water sensor defective, pump blocked or
                                defective, pump output too low
F.23                        Water shortage, temperature difference between flow
                                and return NTC too large
                                Pump blocked or defective, pump output too low, flow and return
                                NTC interchanged
F.24                         Water shortage, temperature rise too quick
                                Pump blocked, insufficient pump output, air in appliance, water
                                pressure too low
F.25                        interruption in the compact thermal module cable harness
                                Compact thermal module cable harness defective
F.27                         Incorrect sensing of flame Flame detector defective
F.28                        Appliance does not start: Attempts to ignite during start
                                failed
                                Faults in the gas supply such as:
                                - Gas meter or gas pressure detector defective
                                - Air in gas
                                - Gas flow pressure too low
                                - Fire protection tap has disengaged
                                Faults in the gas valve, wrong gas setting, igniter (ignition
                                transformer, ignition cable, ignition plug) defective, ionisation
                                current stopped (cable, electrode), faulty earthing in appliance,
                                electronics defective
F.29                        Flame goes off during operation and subsequent ignition
                                attempts failed
                                Gas supply temporarily stopped, faulty earthing of appliance
F.32                         Fan speed variation
                                Fan blocked, plug not inserted correctly on fan, hall sensor
                                defective, fault in cable harness, electronics defective
F.49                     eBUS undervoltage
                            Short circuit on eBUS, overload on eBUS or two power sources on
                             eBUS with different polarity
F.61                     Gas–valve control defective
                            Short circuit/earth (ground) leak in cable harness to gas valves, gas
                            valve assembly defective (earth/ground leak from coils), electronic
                            control system defective
F.62                     Gas valve shutoff delay Gas valve leaking, electronics defective
F.63                     EEPROM error Electronics defective
F.64                     Electronics/NTC fault Short-circuit in flow or return NTC or electronics defective
F.65                     Electronics temperature too high Electronics too hot due to external effect, electronics defective
F.67                    Flame detector input signal is outside the limits
                            (0 or 5 V)
                            Electronics defective
F.70                     No valid DSN in display and/or mainboard
                            Spare part failure display and maiboard interchanged at same time
                            and device specific number not adjusted
F.71                     Flow NTC reports constant value (stuck at) Flow NTC is defective
F.72                     Flow and/or return NTC fault Flow and/or return NTC is defective (tolerances too big)
F.73                     Water pressure sensor signal out of range (too low)
                            Cable to water pressure sensor is broken or has a short-circuit at
                             0 V or water pressure sensor defective
F.74                     Water pressure sensor signal out of range (too high)
                            Cable to water pressure sensor has a short-circuit at 5 V / 24 V or
                            internal fault in water pressure sensor
F.75                     No pressure rise was detected on turning on the pump
                            Water pressure sensor or/and pump defective
                            Air in the heating system, quick bleeder defective
                            Too little water in appliance; check adjustable by-pass; connect
                            external expansion vessel to return
F.76                    Overheating protection on primary heat exchanger triggered
                            Cable or cable connection of fuse in the primary heat exchanger
                            defective, or primary heat exchanger defective
F.77                    condensate pump or feedback of accessories blocks heating
                            condensate pump defective or flume flap feedback triggered
F.78                     wrong configuration with accessory link box VR65 connected to combination boiler
                            con no communication to main board connection error display main board